Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 31

Advertising
background image

Publication 1762-UM003A-EN-P - February 2003

Installation and Wiring 2-13

2-Wire RTD Configuration

3-Wire RTD Configuration

IMPORTANT

Using 2-wire configurations does not permit the
module to compensate for resistance error due to
lead wire length. The resulting analog data includes
the effect of this uncompensated lead wire resistance.
The module continues to place the uncompensated
analog data in the input data file, but the open-circuit
status bit (OCx) is set in word 4 of the input data file
for any enabled channel using a 2-wire configuration.
These status bits may be used in the control program
to indicate that the analog data includes error due to
uncompensated lead wires. See page 3-4 for a
detailed discussion of the open-circuit status bits.

EXC 2

SENSE 2

RTN 2

NC

Belden 9501 Shielded Cable

Cable Shield (to Ground)

RTD EXC

Return

RTD EXC

Return

EXC 2

SENSE 2

RTN 2

NC

Belden 83503 or 9533 Shielded Cable

Cable Shield (to Ground)

RTD EXC

Sense

RTD EXC

Return

Sense

Return