Module Data, Status, and Channel Configuration 3-11

Figure 3.1 Linear Relationship Between Temperature and Proportional Counts

The value +32767 corresponds to the highest value for the device. For
example, if a 100

platinum 385 RTD is selected, the lowest

temperature of -200

°

C corresponds to -32768 counts. The highest

temperature of 850

°

C corresponds to +32767 counts. See Determining

Effective Resolution and Range on page 3-20.

Scaling Examples

+ 32,767

-32,768

850 ˚C

±200 ˚C

Counts

°C

EXAMPLE

Scaled-for-PID to Engineering Units x1

input type = 200

Platinum RTD

• α

= 0.00385°C

range = -200 to +850°C S

LOW

= -200°C S

HIGH

= +850°C

channel data = 3421(scaled-for-PID)

Engineering Units Equivalent = S

LOW

+ (S

HIGH

- S

LOW

) x (channel data/16383)]

Engineering Units Equivalent = -200°C + [(+850°C -(-200°C)) x (3421/16383)] =
19.25°C