Wiring resistance devices (potentiometers) -14, Wiring resistance devices (potentiometers) – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 32

Advertising
background image

Publication 1762-UM003A-EN-P - February 2003

2-14 Installation and Wiring

4-Wire RTD Configuration

Wiring Resistance Devices (Potentiometers)

Potentiometer wiring requires the same type of cable as that for the
RTDs described on page 2-9. Potentiometers can be connected to the
module as a 2-wire or 3-wire connection as shown on page 2-14.

2-Wire Potentiometer Interconnection

EXC 2

SENSE 2

RTN 2

NC

Belden 83503 or 9533 Shielded Cable
Leave one sensor wire open.

Cable Shield (to Ground)

RTD EXC

Return

RTD EXC

Return

Sense

Sense

EXC 2

SENSE 2

RTN 2

NC

EXC 2

SENSE 2

RTN 2

NC

Cable Shield (to Ground)

Potentiometer

RTD EXC

Return

Cable Shield (to Ground)

Potentiometer

RTD EXC

Return

Belden 9501 Shielded Cable

Belden 9501 Shielded Cable

TIP

The potentiometer wiper arm can be connected to
either the EXC or return terminal depending on
whether you want increasing or decreasing
resistance.