Configuration data file -6, Configuration data file – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual
Page 40

Publication 1762-UM003A-EN-P - February 2003
3-6 Module Data, Status, and Channel Configuration
Configuration Data File
The configuration data file is shown below. Bit definitions are
provided in Channel Configuration on page 3-7. Detailed definitions
of each of the configuration parameters follows the table.
The default configuration of the table is all zeros, which yields the
following.
TIP
Normal channel configuration is done using
programming software. In that case, it is not
necessary to know the meaning of the bit
location. However, some systems allow
configuration to be changed by the control
program. Refer to your controller’s
documentation for details.
Table 3.2 Default Configuration
Parameter
Default Setting
Channel Enable/Disable
Disable
Data Format
Raw/Proportional
Input/Sensor Type
100
Ω
Platinum 385
Temperature Units/Mode
°C (not applicable with Raw/Proportional)
Open/Broken Circuit Response
Upscale
Cyclic Lead Compensation
Enable
Excitation Current
1.0 mA
Input FIlter Frequency
60 Hz