Error codes, Error codes -7 – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 75

Advertising
background image

Publication 1762-UM003A-EN-P - February 2003

Diagnostics and Troubleshooting 4-7

Error Codes

The table below explains the extended error code.

Table 4.3 Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Module-Specific
Hardware Error

X300

001

1 0000 0000

General module hardware error

X301

001

1 0000 0001

Microprocessor hardware error

X302

001

1 0000 0010

A/D converter error

X303

001

1 0000 0011

Calibration error

Module-Specific
Configuration
Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid input filter selected (channel 0)

X402

010

0 0000 0010

Invalid input filter selected (channel 1)

X403

010

0 0000 0011

Invalid input filter selected (channel 2)

X404

010

0 0000 0100

Invalid input filter selected (channel 3)

X405

010

0 0000 0101

Invalid input format selected (channel 0)

X406

010

0 0000 0110

Invalid input format selected (channel 1)

X407

010

0 0000 0111

Invalid input format selected (channel 2)

X408

010

0 0000 1000

Invalid input format selected (channel 3)

X409

010

0 0000 1001

Invalid excitation current for input range selected (channel 0)

X40A

010

0 0000 1010

Invalid excitation current for input range selected (channel 1)

X40B

010

0 0000 1011

Invalid excitation current for input range selected (channel 2)

X40C

010

0 0000 1100

Invalid excitation current for input range selected (channel 3)

X40D

010

0 0000 1101

Reserved bits set

(1) X represents the “Don’t Care” digit.

Advertising