B-2 Configuring the 1762-IR4 Module Using RSLogix 500

The default configuration is as follows:

Configuration Using
RSLogix 500 Version 5.50 or
Higher

This example takes you through configuring your 1762-IR4
RTD/resistance input module with RSLogix 500 programming
software. It assumes that your module is installed as expansion I/O in
a MicroLogix 1200 system, that RSLinx™ is properly configured, and
that a communications link has been established between the
MicroLogix processor and RSLogix 500.

Start RSLogix and create a MicroLogix 1200 application. The following
screen appears:

Table B.1 Default Configuration

Parameter

Default Setting

Channel Enable/Disable

Disable

Input Type

100

Platinum 385

Data Format

Raw/Proportional

Temperature Units

°C (not applicable with Raw/Proportional)

Broken Input

Upscale

Disable Cyclic Lead Compensation

Enable

Excitation Current

1.0 mA

Input FIlter Frequency

60 Hz