Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 46

Advertising
background image

Publication 1762-UM003A-EN-P - February 2003

3-12 Module Data, Status, and Channel Configuration

EXAMPLE

Engineering Units x1 to Scaled-for-PID

input type = 200

Platinum RTD

• α

= 0.00385°C

range = -200 to +850°C S

LOW

= -200°C S

HIGH

= +850°C

desired channel temperature = 344°C (engineering units)

Scaled-for-PID Equivalent = 16383 x [(desired ch. temp. - S

LOW

)/(S

HIGH

- S

LOW

)]

Scaled-for-PID Equivalent = 16383 x [(344°C - (-200°C))/(850°C - (-200°C))] = 8488

EXAMPLE

Proportional Counts to Engineering Units x1

input type = 1000

potentiometer

range = 0 to 1000

S

LOW

= 0

S

HIGH

= 1000

channel data = 21567 (proportional counts)

Engineering Units Equivalent =
S

LOW

+ {(S

HIGH

- S

LOW

) x [(ch. data + 32768)/65536]}

Engineering Units Equivalent =
0 + {(1000 - 0) x [(21567 + 32768)/65536]} = 829

EXAMPLE

Engineering Units x1 to Proportional Counts

input type = 3000

potentiometer

range = 0 to 3000

S

LOW

= 0

S

HIGH

= 3000

desired channel resistance = 1809

(engineering units x 1)

Prop. Counts Equivalent =
{65536 x [(ch. resistance - S

LOW

)/(S

HIGH

- S

LOW

)]} - 32768

Proportional Counts Equivalent =
{65536 x [(1809

-

0) / (3000 − 0) ] } − 32768

= 6750

Advertising