A - specifications, General specifications, Appendix a – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 77: Specifications, Appendix

Advertising
background image

1

Publication 1762-UM003A-EN-P - February 2003

Appendix

A

Specifications

General Specifications

Specification

Value

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in (depth) x 1.58 in (width)
height including mounting tabs is 4.33 in.

Approximate Shipping Weight
(with carton)

260g (0.57 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +55°C (32°F to +131°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak

Shock

Operating: 30G

Agency Certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA
C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity (EN61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (EN61000-4-3)

10 V/m , 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier

Fast Transient Burst (IEC1000-4-4)

2 kV, 5kHz

Surge Immunity (EN61000-4-5)

1 kV galvanic gun

Conducted Immunity (EN61000-4-6)

10 V, 0.15 to 80MHz

(1)

(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.