Installation and Wiring 2-5

Mounting

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50.8 mm (2 in.) of space on all sides for adequate
ventilation, as shown below:

ATTENTION

!

Do not remove protective debris strip until after the
module and all other equipment near the module is
mounted and wiring is complete. Once wiring is
complete and the module is free of debris, carefully
remove the protective debris strip. Failure to remove
the strip before operating can cause overheating.

TIP

1762 I/O may be mounted horizontally only.

ATTENTION

!

During DIN rail or panel mounting of all devices, be
sure that all debris (metal chips, wire strands, etc.) is
kept from falling into the module. Debris that falls
into the module could cause damage at power up.