Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual
Page 88

Publication 1762-UM003A-EN-P - February 2003
B-6 Configuring the 1762-IR4 Module Using RSLogix 500
Configuration Using
RSLogix 500 Version 5.2 or
Lower
If you do not have version 5.5 or higher of RSLogix 500, you can still
configure your module, using the Generic Extra Data Configuration
dialog.
To configure the 1762-IR4, select "Other -- Requires I/O Card Type ID"
from the I/O Configuration dialog. The following screen appears.
Enter the I/O module information as shown.
The 1762-IR4 uses six 16-bit binary numbers to configure each of its
four channels. To properly configure and enable input channel 1 for
the setting in the table below, add the decimal values given to each of
the six parameters. These decimal values are listed in Table 3.4,
‘Channel Configuration Bit Definitions,’ on page 3-8.
Table B.B 1762-IR4 Parameter Decimal Values
Parameter
Setting
Decimal Value
Input Type
200
Ω
Platinum 385
256
Data Format
Engineering Units x 10
16384
Temperature Units
Degrees F
128
Broken Input
Upscale
0
Disable Cyclic Lead
Compensation
Enable
0
Excitation Current
1.0 mA
0
Input Filter Frequency
250 Hz
3
Channel Enable/Disable
Enable
-32768
Total -15997