Publication 1762-UM003A-EN-P - February 2003

Chapter

3

Module Data, Status, and Channel
Configuration

After installing the 1762-IR4 RTD/resistance input module, you must
configure it for operation, usually using the programming software
compatible with the controller (for example, RSLogix 500™). Once
configuration is complete and reflected in ladder logic, you will need
to get the module up and running and then verify its operation. This
chapter includes information on the following:

module memory map

accessing input image file data

configuring channels

configuring periodic calibration

preparing ladder logic to reflect the configuration

running the module

verifying the configuration

Module Memory Map

The module uses six input words for data and status bits (input
image), and five configuration words.

Channel 2 Data Word

Channel 0 Data Word

Word 0
Word 1
Word 2
Word 3
Word 4
Word 5

Channel 1 Data Word

Channel 3 Data Word

Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word

Word 0
Word 1
Word 2
Word 3

Input Image

6 words

Configuration

File

5 words

slot e

slot e

Input Image

File

Configuration

File

Bit 15

Bit 0

General/Open-Circuit Status Bits

Over-/Under-range Bits

Enable Calibration Word

Word 4