Publication 1769-UM008A-EN-P - November 2001

1-6 Overview

Module Operation

Module Block Diagram

The module’s input channel circuitry consists of four differential
analog inputs multiplexed into a single analog-to-digital (A/D)
converter. The A/D converter reads the selected input signal and
converts it to a digital value which is presented to the controller. The
multiplexer sequentially switches each input channel to the module’s
A/D converter. The module’s output channel uses a digital-to-analog
(D/A) converter to read the digital output data from the controller and
convert it to an analog output signal. See the block diagram below.

Module Calibration

The module’s input/output channel calibration is guaranteed by its
design. No field calibration is required.

Vin+

Vout+

Iout+

ANLG COM

Iin+

V/Iin-

CH0

CH0

CH1

CH1

CH2

CH3

A-GND

A-GND

A-GND

Vref

VREF

AIN+

A/D

MCU

ASIC

VA3

VA2

VA3

VA2

VA2

VA2

VA1

VA3

VA1

VS1

VS1

VS2

TXD

RXD

A-GND

A-GND

S-GND

D/A

Input

(same as CH0)

Channel Select

DC/DC

Power

Supply

Galvanic
Isolation

Mu

lt

ip

le

xe

r

Bus

Output

(same as CH0)

Advertising