Configuration data file, Output data resolution and format -8, Configuration data file -8 – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 52: Output data resolution and format

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

4-8 1769-IF4XOF2 Module Data, Status, and Configuration Channels

Output Data Resolution and Format

The resolution of an analog output channel depends on the output
type/range and data format selected. The following table provides
detailed resolution information for the module.

Configuration Data File

The configuration file allows you to enable or disable an input or
output channel. It also allows you to configure the operation of the
outputs during a mode change to Program or a Fault condition.
Word 0 bits 4, 5, 6 and 7 allow the individual input channels to be
enabled or disabled. Word 1 bits 4 and 5 allow the individual output
channels to be enabled or disabled.

Table 4.5 Output Resolution

Full Output Range

RAW/Proportional Data

Significant Bits

Resolution per LSB

Decimal
Representation of
Output

Count Value

0V to 10.5 V dc

Sign + 8 bits

41.18mV

0 to 32640

128 (1LSB)

0 mA to 21 mA

Sign + 8 bits

82.35mA

0 to 32640

128 (1LSB)

TIP

Not all controllers support program access to the
configuration file. Refer to your controller’s user
manual.

Advertising