4-8 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Output Data Resolution and Format
The resolution of an analog output channel depends on the output
type/range and data format selected. The following table provides
detailed resolution information for the module.
Configuration Data File
The configuration file allows you to enable or disable an input or
output channel. It also allows you to configure the operation of the
outputs during a mode change to Program or a Fault condition.
Word 0 bits 4, 5, 6 and 7 allow the individual input channels to be
enabled or disabled. Word 1 bits 4 and 5 allow the individual output
channels to be enabled or disabled.
Table 4.5 Output Resolution
Full Output Range
RAW/Proportional Data
Significant Bits
Resolution per LSB
Decimal
Representation of
Output
Count Value
0V to 10.5 V dc
Sign + 8 bits
41.18mV
0 to 32640
128 (1LSB)
0 mA to 21 mA
Sign + 8 bits
82.35mA
0 to 32640
128 (1LSB)
TIP
Not all controllers support program access to the