Valid output data word formats/ranges – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 59

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-15

Valid Output Data Word Formats/Ranges

The analog output data received at the module is converted to
RAW/proportional data format. Unlike the 1769-IF4 and 1769OF2.
on-board scaling is not provided by the module. You must do this via
your control program.

The following table shows the valid output data format for the data
range provided by the module.

Table 4.10 Valid Output Data

Output Range

Output Value

Example Data

Output Range

Condition

Raw/Proportional Data

Decimal Range

0 to 10V dc

Over +10.5V dc

N/A

N/A

(1)

(1) The module’s maximum range is 10.5V or 21 mA. An over-range flag is set at either value. This flag automatically resets when the output data is below the over-range

value.

N/A

+10.5V dc

+ 10.5V dc

Over-range

(1)

32640

0.0V dc to

+10.0V dc

+10.0V dc

Normal

31104

+5.0V dc

Normal

15488

0.0V dc

Normal

0

0 to 20mA

Over 21.0 mA

N/A

N/A

(1)

N/A

21.0 mA

21.0 mA

Over-range

(1)

32640

0.0 mA to 20.0 mA

20.0 mA

Normal

31104

10.0 mA

Normal

15488

0.0 mA

Normal

0