Input/output/configuration data registers -2, Input/output/configuration data registers – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 46

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

4-2 1769-IF4XOF2 Module Data, Status, and Configuration Channels

Input/Output/Configuration Data Registers

Data registers are available for input, output, and configuration. There
are eight input data registers, six configuration registers, and two
output data registers. The module and programming software applies
the following default values to the registers:

Table 4.1 Data Registers

Register

Function

Default at

Power-Up

Programming Software

Default Down Load

C:0

Configuration Word 1

0000h

0000h

C:1

Configuration Word 2

0000h

0000h

C:2

Configuration - Channel 0
Fault Value

0000h

0000h

C:3

Configuration - Channel 0
Program Value

0000h

0000h

C:4

Configuration - Channel 1
Fault Value

0000h

0000h

C:5

Configuration - Channel 1
Program Value

0000h

0000h

I:0

Channel 0 Input Word

0000h

I:1

Channel 1 Input Word

0000h

I:2

Channel 2 Input Word

0000h

I:3

Channel 3 Input Word

0000h

I:4

Input Channel Over-range

0000h

I:5

Output Channel Over-range

0000h

I:6

Channel 0 Output Data Echo

0000h

I:7

Channel 1 Output Data Echo

0000h

O:0

Channel 0 Output Word

0000h

0000h

O:1

Channel 1 Output Word

0000h

0000h

Advertising