Extended error codes -5, Extended error codes, Extended_error_info field – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 65

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

Module Diagnostics and Troubleshooting 5-5

Extended_Error_Info Field

Check the Extended_Error_Info field when a non-zero value is in the
Mod_Error field. The following are some Extended_Error_Info error
codes:

Extended Error Codes

When invalid values are entered in the configuration file, the module
ignores the invalid configuration, generates a non-critical error, and
keeps operating with the previous configuration. The following table
explains the extended error codes for the 1769-IF4XOF2 analog
combination module:

Table 5.1 Extended Error Information Field

Error Type

Mod_Error (11:9)

Extended_Error_Info (8:0)

No Error

0

always 000

Hardware Error

1

000 = no additional information
001 = Power-up Reset
002 to 0FF = general common errors
100 to 1FF = module specific errors

Configuration Error

2

000 = no additional information
001 to 1FF = module specific errors

Table 5.2 Extended Error Codes

Error Type

Hex
Equivalent

(1)

Module
Error
Code
Bits (11:9)

Extended Error
Information
Code Bits 8:0

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General Hardware Error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

1 0000 0000

General hardware error (ASIC)

X301

001

1 0000 0001

Microprocessor hardware error

1769-IF4XOF2 Specific
Configuration Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

invalid Fault Value Entered for (channel 0)

X402

010

0 0000 0010

invalid Fault Value Entered for (channel 1)

X403

010

0 0000 0011

invalid Program Value Entered for (channel 0)

X404

010

0 0000 0100

invalid Program Value Entered for (channel 1)

(1) X represents the “Don’t Care” digit.

Advertising