Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 75

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

Module Addressing and Configuration with MicroLogix 1500 B-3

1769-IF4XOF2 Configuration File

The configuration file allows you to enable or disable the modules
input and/or output channels. It also allows you to select how the
Program or Fault mode condition and what the output value will be if
the User-defined Safe State is selected. The configuration file is
explained in more detail in Configuration Data File on page 4-8.

The configuration file is modified using the programming software
configuration screen. For an example of module configuration using
RSLogix 500.

Configuring 1769-IF4XOF2 in
a MicroLogix 1500 System

This example takes you through configuring your 1769-IF4XOF2
analog module with RSLogix 500 programming software. This
application example assumes your module is installed as expansion
I/O in a MicroLogix 1500 system, and that RSLinx™ is properly
configured and a communications link has been established between
the MicroLogix processor and RSLogix 500.

TIP

The RSLogix 500 configuration default is to enable
each analog input channel. For improved analog
input module performance, disable any unused
channels.

Table B.1 Software Configuration Channel Defaults

1769-IF4XOF2

Parameter

Default Setting

Enable/Disable Input/Output Channel

Disabled

Program Mode (Outputs)

Hold Last State

Fault Mode (Outputs)

Hold Last State

Advertising