The 1769-IF4XOF2 module is configured for current or voltage
operation by proper wiring of the analog I/O device to the module.
However, a channel is enabled using its configuration file.

The configuration file is typically modified using the programming
software configuration screen. It can also be modified through the
control program, if supported by the controller. See the configuration
file chart on page 4-8.

For an example of module configuration using MicroLogix 1500 and
RSLogix 500, see Appendix B. For an example of module
configuration using CompactLogix and RSLogix 5000, see Appendix C.

Step 5:

Configure the module

Reference

Chapter 4
(Module Data, Status, and
Configuration Channel for
1769-IF4XOF2)

Table 2.1 Configuration Data File

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Not Used

(1)

EI3

EI2

EI1

EI0

FM0

(2)

PM0

(2)

Not

Used

(1)

PFE0

(2)

1

Not Used

(1)

EO1

EO0

FM1

(2)

PM1

(2)

Not

Used

(1)

PFE1

(2)

2

SGN

Channel 0 Fault Value

(2)

0

0

0

0

0

0

0

3

SGN

Channel 0 Program (Idle) Value

(2)

0

0

0

0

0

0

0

4

SGN

Channel 1 Fault Value

(2)

0

0

0

0

0

0

0

5

SGN

Channel 1 Program (Idle) Value

(2)

0

0

0

0

0

0

0

(1) Any attempt to write a non-valid (1’s) bit configurations into any not used selection field results in a module configuration er ror.
(2) Not all controllers support these functions. Refer to your controller’s user manual for details.