Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 33

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

Installation and Wiring 3-11

Outputs

Voltage outputs (Vout 0+ and Vout 1+) of the module are
referenced to ANLG COM. Load resistance for a voltage output
channel must be equal to or greater than 1K

.

Current outputs (Iout 0+ and Iout 1+) of the module source
current that returns to ANLG COM. Load resistance for a current
output channel must remain between 0 and 300

.

Effect of Transducer/Sensor and Cable Length Impedance on Voltage Input
Accuracy

For voltage inputs, the length of the cable used between the
transducer/sensor and the module can affect the accuracy of the data
provided by the module.

Where:

Rc = DC resistance of the cable (each conductor) depending on
cable length

Rs = Source impedance of analog transducer/sensor input

Ri = Impedance of the voltage input (150 K

)

Vs = Voltage source (voltage at the transducer/sensor input
device)

Vin = Measured potential at the module input

%Ai = Percent added inaccuracy in a voltage-based system due
to source and cable impedance.

ATTENTION

!

Be careful when stripping wires. Wire fragments
that fall into a module could cause damage at
power up. Once wiring is complete, ensure the
module is free of all metal fragments.

V in

Vs

Ri

Rc

Rc

Rs

+

-

Vin

Ri

Vs

×

[

]

Rs

2

Rc

×

(

)

Ri

+

+

[

]

-------------------------------------------------------

=

Advertising