Minimum spacing -7 panel mounting -7, Minimum spacing, Panel mounting – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual
Page 29: Panel mounting using the dimensional template

Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-7
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation,
as shown below:
Panel Mounting
Mount the module to a panel using two screws per module. Use M4
or #8 panhead screws. Mounting screws are required on every
module.
Panel Mounting Using the Dimensional Template
Host Controller
Co
m
pac
t I/
O
Co
m
pac
t I/
O
Co
m
pac
t I/
O
Co
m
pac
t I/
O
Co
m
pac
t I/
O
End C
ap
Side
Side
Top
Bottom
132
(5.197)
122.6±0.2
(4.826±0.008)
35
(1.38)
28.5
(1.12)
Com
pact
I/
O
Com
pact
I/
O
Com
pact
I/
O
Ho
st
C
on
tr
ol
le
r
Refer to host controller documentation for this dimension.
For more than 2 modules: (number of modules-1) X 35 mm (1.38 in.).
Ri
ght
End
C
ap
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.04 mm (0.016 in.).