5-6 Module Diagnostics and Troubleshooting

Module Condition Errors

Common Hardware Errors

There are several general common hardware errors. The following
table lists these errors.

Hardware Specific Errors

If the module detects that any of the analog to digital converters are
not functioning properly, one of the following hardware errors is set:

Module Inhibit Function

Some controllers support the module inhibit function. See your
controller manual for details.

Whenever the combination module is inhibited, it enters the program
mode and the output channels are changed to the state configured for
the program mode. The input channels of the module continue to
provide information about changes at its inputs to the 1769 Compact
Bus Master (for example, a CompactLogix controller).

Table 5.3 Common Hardware Errors

Mod_Error

(11:9)

Extended_Error

_Info (8:0)

Error Description

0

000

No Errors

1

000

General hardware error; no additional
information

1

001

Power-up reset state

Table 5.4 Specific Hardware Errors

Mod_Error

(11:9)

Extended_Error

_Info (8:0)

Error Description

1

100

General H/W error (ASIC)

1

101

Microprocessor H/W error

1

102

SPARE (not part of 1769-IF4XOF2 design)

1

103

SPARE (not part of 1769-IF4XOF2 design)