Module Input Update Time and Scanning Process

The module input update time is defined as the time required for the
module to sample and convert the input signals of all 4 enabled input
channels and provide the resulting data values to the processor.

Module update time can be calculated by adding the sum of all
enabled channel times. Channel times include channel scan time,
channel switching time, and reconfiguration time. The module
sequentially samples the channels in a continuous loop. The table
below shows module update times, based on the number of input
channels enabled.

Maximum Input Response Time of Module (5 ms)

Minimum Input Response

Time of Module (5 ms)

Input Signal

Input After Filter

A/D Conversion (4 CH)

MPU/ASIC Input Data

Communication

MPU/ASIC Output Data

Communication

Output D/A Conversion

Input Update Time (4.5 ms)

Table 4.8 Module Update Time

Number of Enabled Input Channels

Typical Update Time

(1)

(1) Each enabled output channel adds 0.02 ms to the typical module update time.

0

1.3 ms

1

2.1 ms

2

2.9 ms

3

3.7 ms

4

4.5 ms