Terminal door label -18, Terminal door label, Wiring diagram showing differential inputs – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual

Page 40

Advertising
background image

Publication 1769-UM008A-EN-P - November 2001

3-18 Installation and Wiring

Terminal Door Label

A removable, write-on label is provided with the module. Remove the
label from the door, mark the identification of each terminal with
permanent ink, and slide the label back into the door. Your markings
(ID tag) will be visible when the module door is closed.

Wiring Diagram Showing Differential Inputs

V in 0 +

V in 1 +

V/I in 0 -

V/I in 1 -

I in 0 +

I in 1 +

V in 2 +

V in 3 +

V/I in 2 -

V/I in 3 -

I in 2 +

I in 3 +

ANLG Com

ANLG Com

V out 0 +

V out 1 +

I out 1 +

I out 0 +

1769-IF4XOF2

V/I in 0 -

ANLG

Com

I out 0 +

I in 0 +

V in 2 +

V/I in 2 -

I in 2+

V out 0 +

V in 0 +

V/I in 1 -

ANLG

Com

I out 1 +

I in 1 +

V in 3 +

V/I in 3 -

I in 3 +

V out 1 +

V in 1 +

Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module

D A N G E R

Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.

+

V in 1+

V in 3+

V in 0+

V/I in 0-

I in 1+

I in 3+

V/I in 1 -

I in 0+

I in 2+

V in 2 +

V/I in 3 -

V/I in 2-

ANLG Com

ANLG Com

V out 1+

I out 1+

V out 0+

I out 0+

Belden 8761 cable (or equivalent)

differential voltage

transmitter

1769-IF4XOF2 Terminal Block

earth ground the shield

locally at

the module

(1) All analog commons (ANLG Com) are internally connected.
(2) If multiple power supplies are used, the commons must have the same ground reference.
(3) User Belden 8761 cable (or equivalent) for wiring analog I/O.

Advertising