Message Packet Formats

Chapter 5

5-22

Unprotected Write

This command writes words of data into ay area of PC data table memory.
Use the SIZE field to specify the number of bytes to be read. To specify a
number of PC words, SIZE should be an even value because PC words are
two bytes long.

Command Format:

Reply Format:

TNS

STS

CMD

08

SRC

DST

TNS

STS

CMD

48

SRC

DST

ADDR

DATA — Max of 242 Bytes

PLC Commands

PLC stations can execute all of the commands in the basic command set,
except the commands to set NAKs, ENQs, timeouts, and variables. They
can also execute the following commands, which apply only to PLC
controllers:

Disable Outputs
Enable Program
Enable Scan
Physical Read
Physical Write

The above are privileged commands. This means that only a computer
can initiate them. Their primary purpose is for uploading and
downloading PLC memory.