Message Packet Formats
Chapter 5
5-27
Enter Upload Mode
This command puts the PLC-2 processor into the Upload mode. Use this
command on a PLC-2 station before attempting to send any physical read
commands to the station.
Command Format:
Reply Format:
TNS
STS
CMD
07
SRC
DST
TNS
STS
CMD
47
SRC
DST
FNC
06
When you send an Enter Download/Upload mode command, the
Industrial Terminal port is disabled until you send an Exit
Download/Upload mode command. When the Industrial Terminal port is
disabled, it enters the Mode Select State. In order to leave this state, you
will have to manually select a mode at the Industrial Terminal.
Exit Download/Upload Mode
This command takes the PLC-2 processor out of the Upload or Download
mode. Use this command to restart the PLC-2 processor after performing
an upload or download operation.
If you don’t send this command after a Download/Upload mode
command, you will have to recycle power at the 1771-KA or 1771-KA2
module to enable Industrial Terminal communication.
Command Format:
Reply Format:
TNS
STS
CMD
07
SRC
DST
TNS
STS
CMD
47
SRC
DST
FNC
05