Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual

Page 169

Advertising
background image

Error Reporting

Chapter 7

7Ć14

Code (If Applies)

EXT STS STS

Error

Code

Meaning

DIAGNOSTIC READ COMMAND

10

81

1. A 2Ćbyte ADDR field and a 1Ćbyte SIZE field are missing

after the FNC byte in the command message.

2. The number of bytes of data requested in the SIZE field is

greater than the maximum number allowed per reply packet

(244), or SIZE is 0 (zero).

50

85

The command is an illegal request to read from the 1775ĆKA

module's backplane window.

DIAGNOSTIC STATUS COMMAND

40

84

A backplane error occurred during determination of the physical

address of the end of the ladder diagram program or of the end of

user memory.

PLC/PLCĆ2 WORD WRITE COMMANDS

10

81

1. A 2Ćbyte ADDR field is expected after the TNS word, but

only one byte is present.

2. There is an odd number of data bytes in the command

packet.

3. The ADDR value is odd (that is, it does not specify a word

address).

30

83

The local 1775ĆKA module has executed a shutdown request to

the local PLCĆ3 processor.

40

84

Local PLCĆ3 backplane error (either memory parity or

timeout/disconnect).

50

85

1. The destination file does not exist in PLCĆ3 memory.

2. The destination word does not exist in the destination PLCĆ3

file.

3. The length of the destination file is greater than

65, 535 words.

60

86

Local keyswitch setting prohibits writing into desired destination

file.

70

87

The local PLCĆ3 processor is in Program mode. There may or

may not be a major system fault.