Message packet formats chapter 5 – Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual
Page 111

Message Packet Formats
Chapter 5
5-32
Download Request
A computer can use this command to inform the 1775-KA module that it
wants to do a download. If the 1775-KA module grants the download
privilege, the computer may begin issuing physical reads or writes. If a
different station already has the download privilege, the second station is
denied the privilege.
Reply Format:
(EXT STS Byte Optional)
B.
Format When Reporting an Error
TNS
STS
CMD
4F
SRC
DST
TNS
STS
CMD
4F
SRC
DST
EXT
STS
A.
Format When Successful Execution
Command Format:
TNS
STS
CMD
0F
SRC
DST
FNC
05
File Read
This is a read command, starting address of which is either a file symbol
or a block address. This starting address must point to a file of words.
The function code is 4.
TNS
DST
SRC
CMD
FNC
0F
04
PACKET
OFFSET
TOTAL
TRANS
PLC-3 LOGICAL ADDRESS
(2-51 Bytes)
SIZE
STS
TNS
STS
CMD
4F
SRC
DST
TNS
STS
CMD
4F
SRC
DST
EXT
STS
DATA — Max. of 244 Bytes
or 122 Words
Command Packet:
Reply Format:
(EXT STS Byte Is Optional)
B.
Format When Reporting an Error
A.
Format When Successful Execution