Message packet formats chapter 5 – Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual

Page 111

Advertising
background image

Message Packet Formats

Chapter 5

5-32

Download Request

A computer can use this command to inform the 1775-KA module that it
wants to do a download. If the 1775-KA module grants the download
privilege, the computer may begin issuing physical reads or writes. If a
different station already has the download privilege, the second station is
denied the privilege.

Reply Format:

(EXT STS Byte Optional)

B.

Format When Reporting an Error

TNS

STS

CMD

4F

SRC

DST

TNS

STS

CMD

4F

SRC

DST

EXT

STS

A.

Format When Successful Execution

Command Format:

TNS

STS

CMD

0F

SRC

DST

FNC

05

File Read

This is a read command, starting address of which is either a file symbol
or a block address. This starting address must point to a file of words.
The function code is 4.

TNS

DST

SRC

CMD

FNC

0F

04

PACKET
OFFSET

TOTAL
TRANS

PLC-3 LOGICAL ADDRESS
(2-51 Bytes)

SIZE

STS

TNS

STS

CMD

4F

SRC

DST

TNS

STS

CMD

4F

SRC

DST

EXT

STS

DATA — Max. of 244 Bytes

or 122 Words

Command Packet:

Reply Format:

(EXT STS Byte Is Optional)

B.

Format When Reporting an Error

A.

Format When Successful Execution

Advertising