Message Packet Formats

Chapter 5

5-13

Table 5.B Continued
Contents of Status DATA for 1771-KA2, -KC/KD, -KE/KF; 1770-KF2; 1771-KG, 1774-KA; and
1785-KA Modules

Byte

Bit

Value

Meaning

10 Cont’d

1771-KG MODULE

0

0
1

Half-Duplex Protocol
Full-Duplex Protocol

1

0
1

Physical Writes Enabled
Physical Writes Disabled

2

0
1

Unprotected Commands Enabled
Unprotected Commands Disabled

3

0
1

Embedded Responses Enabled
Embedded Responses Disabled

4

0
1

Even Parity
No Parity

5-7

0
1
2
3
4
5
6
7

19,200

bps

9,600

bps

4,800

bps

2,400

bps

1,200

bps

600

bps

300

bps

110

bps

1774-KA MODULE

0

0
1

Unprotected Commands Enabled
Unprotected Commands Disabled

1

--

Not Used

2

0
1

Physical Writes Enabled
Physical Writes Disabled

3

0
1

Transmission of Unprotected Commands Enabled
Transmission of Unprotected Commands Disabled

4

0
1

Data Highway Port B Is Connected
Data Highway Port A Is Connected

5

0
1

PLC Outputs Held in Last State
PLC Outputs Turned Off

6-7

0
1
2
3

57,600

bps

76,800

bps

38,400

bps

115,200

bps

1770-KF2 MODULE

0-1

0
1
2
3

57,600 Bits per Second
Undefined
Undefined
undefined

2

--

Not Used

3-7

Logical Complement of the State of Option Switch SW-1, Switches 1 through 5

1785-KA MODULE

0

0
1

57,600 Bits per Second

Data Highway Baud Rate Switch

Undefined

1

0
1

57,600 Bits per Second

PCL Baud Rate Switch

Undefined

2-3

--

Not Used

4

--

Not Used

5

--

Not Used

6-7

--

Not Used

11

Address of the PCL Active Node Table

12

(Low Byte First)