Message Packet Formats

Chapter 5

5-16

Table 5.E
Contents of Status DATA for PLC-5

Byte

Bit

Value

Meaning

1

Operating Status of PLC-5 Processor

0-2

0
1
2
3
4
5
6
7

Program Load
Not Used
Run Mode
Not Used
Remote Program Load
Remote Test
Remote Run
Not Used

3

0
1

Normal
Major Processor Fault

4

0
1

Normal
Download Mode

5

--

Not Used

6

0
1

Not Testing Edits
Testing Edits

7

0
1

Not Testing Edits
Testing Edits

2

Processor Type

0-3

11

PLC-5

4-7

11

PLC-5

3-6

Size of User Memory (Low Word First, Low Byte First)

7

Series and Revision of PLC-5

0-4

0
1

Revision A
Revision B, Etc.

5-7

0
1

Series A
Series B, Etc.

8

Processor Number on PCL Link

9

I/O Address — Address of the processor if it is an adapter. If it is a scanner, then value is
0FDH.

10

I/O and Communication Parameters

0
1
2
5
6

0
1
1
1
1

Double Density
Adapter Mode
Module Group 4 Top Half
Adapter Is Half Rack
PCL at 115K Baud

11-12

Number of Data Table Files (Low Byte First)

13-14

Number of Program Type Files (Low Byte First)

15

Forcing Status

0
4

1
1

Forces Active
Forces Are Present in the Tables

16

Memory Protect Indication — Non-Zero means memory is protected.

17

Bad RAM Indication — Non-Zero means RAM is bad, must be cleared.