Message packet formats chapter 5 – Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual
Page 95

Message Packet Formats
Chapter 5
5-16
Table 5.E
Contents of Status DATA for PLC-5
Byte
Bit
Value
Meaning
1
Operating Status of PLC-5 Processor
0-2
0
1
2
3
4
5
6
7
Program Load
Not Used
Run Mode
Not Used
Remote Program Load
Remote Test
Remote Run
Not Used
3
0
1
Normal
Major Processor Fault
4
0
1
Normal
Download Mode
5
--
Not Used
6
0
1
Not Testing Edits
Testing Edits
7
0
1
Not Testing Edits
Testing Edits
2
Processor Type
0-3
11
PLC-5
4-7
11
PLC-5
3-6
Size of User Memory (Low Word First, Low Byte First)
7
Series and Revision of PLC-5
0-4
0
1
Revision A
Revision B, Etc.
5-7
0
1
Series A
Series B, Etc.
8
Processor Number on PCL Link
9
I/O Address — Address of the processor if it is an adapter. If it is a scanner, then value is
0FDH.
10
I/O and Communication Parameters
0
1
2
5
6
0
1
1
1
1
Double Density
Adapter Mode
Module Group 4 Top Half
Adapter Is Half Rack
PCL at 115K Baud
11-12
Number of Data Table Files (Low Byte First)
13-14
Number of Program Type Files (Low Byte First)
15
Forcing Status
0
4
1
1
Forces Active
Forces Are Present in the Tables
16
Memory Protect Indication — Non-Zero means memory is protected.
17
Bad RAM Indication — Non-Zero means RAM is bad, must be cleared.