Message packet formats chapter 5 – Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual

Page 113

Advertising
background image

Message Packet Formats

Chapter 5

5-34

Physical Write

This is a write command where the starting address is a PLC-3 physical
address. It is used to download to a PLC-3 from a computer. The
destination 1775-KA module will accept this command only after the
source station has successfully transmitted a shutdown request. Function
code for this command is 8.

TNS

DST

SRC

CMD

FNC

0F

08

PLC-3
PHYSICAL ADDRESS

DATA — Max. of 238 Bytes or 119 Words

TNS

STS

CMD

4F

SRC

DST

TNS

STS

CMD

4F

SRC

DST

EXT

STS

STS

Command Packet:

Reply Format:

(EXT STS Byte Is Optional)

B.

Format When Reporting an Error

A.

Format When Successful Execution

Restart Request

This command is used by the computer to terminate an upload or a
download. The computer cannot issue this command until after it has
successfully completed an upload or download operation with the
destination station. This command causes the 1775-KA module to revoke
the upload and download privileges for the source computer station and to
initialize a PLC-3 start.

Reply Format:

(EXT STS Byte Optional)

B.

Format When Reporting an Error

TNS

STS

CMD

4F

SRC

DST

TNS

STS

CMD

4F

SRC

DST

EXT

STS

A.

Format When Successful Execution

Command Format:

TNS

STS

CMD

0F

SRC

DST

FNC

0A

Advertising