Error Reporting

Chapter 7

7Ć16

Code (If Applies)

EXT STS STS

Meaning

Error

Code

PLCĆ3 WRITE COMMANDS

10

81

1. There are not at least 2 bytes of data after the end of the

block address.

2. There is an odd number of data bytes after the end of the

block address.

3. Sum of packet offset and size values specifies more than

65,535 words.

4. Sum of packet offset and size is greater than total

transaction size.

30

83

The local 1775ĆKA module has executed a shutdown request.

40

84

Backplane error (either memory parity or timeout/disconnect).

60

86

Keyswitch setting disallows access.

70

87

Local PLCĆ3 is in Program mode.

1

F0

231

There is an error in converting the block address

(major section > 63, context > 15, or section > 15).

2

F0

232

Three or fewer addressing levels specified in a PLCĆ3 word

address.

3

F0

233

Conversion of a file address to a block address resulted in more

than 9 addressing levels.

4

F0

234

Symbolic address not found.

5

F0

235

Symbolic address is of length zero or is longer than 8 bytes.

6

F0

236

1. Destination file not found.

2. Destination address does not point to a word (for

wordĆrange writes) or a file (for file writes).

3. Destination address specifies more levels than required.

4. First word of destination location does not exist.

7

F0

237

1. Any word in the total transaction does not exist in the

destination file.

2. For a file write, the source and destination files are not the

same size.

8

F0

238

Destination file size changed between packets of a multiĆpacket

transaction and became too small for the total transaction.

9

F0

239

There are more than 65,535 words in the source file.