Message Packet Formats

Chapter 5

5-15

Table 5.D
Contents of Status DATA for 1775-KA Modules

Byte

Bit

Value

Meaning

1

Operating Status of PLC-3 Processor

0-1

0
1
2

Program Mode
Test Mode
Run Mode

2

--

Not Used

3

0
1

Normal
Major Processor Fault

4

0
1

Normal
Shutdown Request

5

0
1

Normal
Shutdown in Effect

6-7

--

Not Used

2

Type of Station Interface

0-3

6
7

1775-KA, Data Highway Port
1775-KA, RS-232-C Port

3

Current Context (Stored in Bits 4 to 7)

4

Thumbwheel Number

5-6

Mode Control Word — The logical address of the mode control word is E0.0.0.8.

7-8

Starting Byte Address of the Diagnostic Counters and Timers — There is a separate
block of diagnostic timers and counters for the Data Highway port and the RS-232-C
port. The address given here is the one for the port that received the diagnostic status
command.

9

Series and Revision Number of the 1775-KA Module

0-4

0
1

Revision A
Revision B, Etc.

5-7

0
1

Series A
Series B, Etc.

10

Not Used

11-14

The Physical Address of the Unused Word of PLC-3 System Memory — This is the
physical address corresponding to the logical address E60.0.0.0.

15-18

The Total Number of Words in the PLC-3 System Memory (Both Used and Unused) —
This is the physical word address that corresponds to the logical address E60.0.0.0.