Rockwell Automation 1770-KF2 Data Highway or Highway Plus Interface Module User Manual User Manual
Page 94

Message Packet Formats
Chapter 5
5-15
Table 5.D
Contents of Status DATA for 1775-KA Modules
Byte
Bit
Value
Meaning
1
Operating Status of PLC-3 Processor
0-1
0
1
2
Program Mode
Test Mode
Run Mode
2
--
Not Used
3
0
1
Normal
Major Processor Fault
4
0
1
Normal
Shutdown Request
5
0
1
Normal
Shutdown in Effect
6-7
--
Not Used
2
Type of Station Interface
0-3
6
7
1775-KA, Data Highway Port
1775-KA, RS-232-C Port
3
Current Context (Stored in Bits 4 to 7)
4
Thumbwheel Number
5-6
Mode Control Word — The logical address of the mode control word is E0.0.0.8.
7-8
Starting Byte Address of the Diagnostic Counters and Timers — There is a separate
block of diagnostic timers and counters for the Data Highway port and the RS-232-C
port. The address given here is the one for the port that received the diagnostic status
command.
9
Series and Revision Number of the 1775-KA Module
0-4
0
1
Revision A
Revision B, Etc.
5-7
0
1
Series A
Series B, Etc.
10
Not Used
11-14
The Physical Address of the Unused Word of PLC-3 System Memory — This is the
physical address corresponding to the logical address E60.0.0.0.
15-18
The Total Number of Words in the PLC-3 System Memory (Both Used and Unused) —
This is the physical word address that corresponds to the logical address E60.0.0.0.