Message Packet Formats

Chapter 5

5-37

Word Range Write

This is a write command whose starting address is either a word symbol, a
file symbol plus a word offset, or a logical address. This starting address
must point to a word in a file. The function code is 0. A special case of
this command is the single-word write, where the number of bytes to read
is only one word long.

Command Format:

TNS

DST

SRC

CMD

00

00

FNC

0F

00

PACKET
OFFSET

TOTAL
TRANS

ASCII SYMBOL
(8 CHARS. MAX.)

DATA — MAX. OF 228 BYTES OR 114 WORDS

W/F
00

TNS

DST

SRC

CMD

FNC

0F

00

PACKET
OFFSET

TOTAL
TRANS

PLC-3 LOGICAL ADDRESS
(2-51 Bytes)

DATA — Max. length is 239 bytes minus the length of the PLC–3 logical address.

STS

(Must be an even number of bytes.)

TNS

STS

CMD

4F

SRC

DST

TNS

STS

CMD

4F

SRC

DST

EXT

STS

Reply Format:

(EXT STS Byte Is Optional)

B.

Format When Reporting an Error

A.

Format When Successful Execution

B.

Logical Address

A.

Word Symbol Address

STS

PLC-4 Commands

PLC-4 stations can execute all of the commands in the basic command
set. They can also execute the following commands, which apply only to
PLC-4 Microtrols:

Allocate Processor
Deallocate Processor
Initialize Processor
Physical Read
Physical Write
Physical Write with Mask
Set to Program Load Mode
Set to Run Mode
Set to Single-Scan Test Mode
Set to Test Mode