Data Encoding and Addressing

Chapter 6

6-16

PLC-3 and PLC-5

PLC-3 and PLC-5 controllers use physical addresses that are related to
logical addresses by means of pointers. Since no two PLC-3/PLC-5
systems are configured identically, the pointers are not fixed. Therefore,
there is no algorithm for converting logical to physical PLC-3 or PLC-5
addresses.

The PLC-3/PLC-5 physical address is a word address. It goes in the
4-byte field labeled “PLC-3 physical ADDR” or “PLC-5 physical ADDR”
in the PLC-3/PLC-5 physical read or write command message format
(Chapter 5). The format for this physical address field is:

PLC-3/PLC-5 Physical Address

First Byte

A24

A23

A22

A21

A20

A19

A18

A17

Second Byte

0

0

0

0

0

0

0

0

Third Byte

A8

A7

A6

A5

A4

A3

A2

A1

Fourth Byte

A16

A15

A14

A13

A12

A11

A10

A9

In this format, A1 through A24 represent the 1 to 24 bits of the physical
address value. For example, to address a command message to Physical
Word Address 12,200 decimal (002FA8 hex), you would use the
following binary code in the address field:

First Byte

0

0

0

0

0

0

0

0

(Value 00 Hex)

Second Byte

0

0

0

0

0

0

0

0

(Always 00 Hex)

Third Byte

1

0

1

0

1

0

0

0

(Value A8 Hex)

Fourth Byte

0

0

1

0

1

1

1

1

(Value 2F Hex)

The recommended procedure for uploading or downloading PLC-3 or
PLC-5 memory is to begin at Physical Address 0000 and proceed
sequentially to the end of memory. Since a single physical read or write
command can transfer only about 120 words of data, it will take many
such commands to upload or download the entire PLC-3 or PLC-5
memory. Therefore, each successive physical read or write should begin
at the next physical address after the one where the previous command
stopped.