Chapter

6

6-1

Diagnosing Faults

This chapter describes how to diagnose faults in a PLC-3 backup system
using:

status indicators on the front panels of processors and on the front

panels of modules in the processors

system status words.

Also, it describes a simple diagnostic technique that can help you identify
the program section and rung number of faults when they occur.

Before discussing fault diagnosis, however, you should review what
happens when a processor encounters a major fault.

If the primary processor determines that a major fault exists while it is in
run mode, the primary processor will:

display the message

DEACTIVE

on the front panel of the primary

processor if a 1775-S4A or -SR is scanner number one; or display the
major fault on the front panel of the primary processor if a 1775-S5 or
-SR5 is scanner number one.

switch to program load mode

pass control to the backup processor

cause a fault message to appear on the screen of a programming

terminal, if one is being used.

Chapter Objectives

How the Backup System

Behaves When a

Major Fault Occurs