Programming Techniques

Chapter 5

5-15

Figure 5.6

Program Compare Status Information for the Memory Communication

Module

Unused value (always 0)

User program section of

PLCĆ3 memory (always 4)

Ladder program section:

1 for main program

2 for subroutine

3 for fault routine

Current operating context number

(1 to 15)

17

16

15

14

13 12

11

10

07

06

05 04

03

02

01

00

17

16

15

14

13 12

11

10

07

06

05 04

03

02

01

00

Status File 4, Word 1 in the Data Table

Status File 4, Word 2 in the Data Table

This word stores the rung number where the

memory communication module detected the

miscomparison

10985ĆI

Word 2 gives you the rung number where the miscomparison occurred. For
example, if word 2 contained the value 12 then, the miscomparison is
located on rung 12 of the ladder logic program section designated in status
file 4, word 0.

1775ĆMX Module System ID

A system ID is automatically assigned to each 1775-MX module and
stored in S4:3 (status file 4, word 3). The MCM OPERATION menu in
LIST also displays this system ID. This ID is dependent on the physical
location (chassis number and slot number) of scanner #1.

17

16

15

14

13 12

11

10

07

06

05 04

03

02

01

00

Status File 4, Word 1 in the Data Table

Number of chassis slot

in which Scanner #1

resides (1 thru 6)

Number of chassis

in which Scanner #1

resides (0 thru 3)

10986ĆI