Diagnosing Faults
Chapter 6
6-7
Table 6.E
Data Highway/Data Highway Plus Status Indicators for 1775ĆS5, ĆSR5
Scanner Modules
Indicator
Status
Description
XMTG
ON
transmitting a message
RCVG
ON
receiving a message
RDY
ON
ready to transmit a message
ERR
ON
programming or communication error detected
DIS
ON
Data Highway/Data Highway Plus channel is disabled
Important: When the scanner is polling, both the XMTG and RCVG
LEDs turn on.
Table 6.F
Status Indicators for 1775ĆMX Memory Communication Modules
Indicator & Status
PRI
B/U
Description
ON
OFF
Processor in primary mode
OFF
ON
Processor in backup mode
OFF
OFF
Processor faulted
ERR
ON
Communication error detected between two memory communication modules
OFF
Communication normal between two memory communication modules
Whenever possible, communication between memory communication
modules will continue even though the ERR indicator is on. If the MX
status area of the data table is created, the ERR indicator remains on until
you reset the communication error bit (S4:0/07).
If you have not created the status section, the error indicator remains on
until the problem causing the communication error is corrected, then it
goes off automatically.