Diagnosing Faults

Chapter 6

6-7

Table 6.E

Data Highway/Data Highway Plus Status Indicators for 1775ĆS5, ĆSR5

Scanner Modules

Indicator

Status

Description

XMTG

ON

transmitting a message

RCVG

ON

receiving a message

RDY

ON

ready to transmit a message

ERR

ON

programming or communication error detected

DIS

ON

Data Highway/Data Highway Plus channel is disabled

Important: When the scanner is polling, both the XMTG and RCVG
LEDs turn on.

Table 6.F

Status Indicators for 1775ĆMX Memory Communication Modules

Indicator & Status

PRI

B/U

Description

ON

OFF

Processor in primary mode

OFF

ON

Processor in backup mode

OFF

OFF

Processor faulted

ERR

ON

Communication error detected between two memory communication modules

OFF

Communication normal between two memory communication modules

Whenever possible, communication between memory communication
modules will continue even though the ERR indicator is on. If the MX
status area of the data table is created, the ERR indicator remains on until
you reset the communication error bit (S4:0/07).

If you have not created the status section, the error indicator remains on
until the problem causing the communication error is corrected, then it
goes off automatically.