Using the 1775ĆMX
Memory Communication Module
Chapter 4
4-15
To enter the program compare limits, do the following:
1.
Select the command PROG COMP LIMITS from the MCM
OPERATION menu by typing:
10 [ENTER]
2.
Enter the program limits into the PROG COMP LIMITS menu using
the following syntax:
m/s/f
where:
m
is the limit for the main program section
s
is the limit for the subroutine program section
f
is the limit for the fault program section
3.
To begin the program compare function, select the command
ENABLE PROG COMP from the MCM OPERATION menu by
typing:
7 [ENTER]
Important: If a limit is modified while a program comparison is in
progress, the new value will not be used until you select the command
ENABLE PROG COMP again.