Using the 1775ĆMX

Memory Communication Module

Chapter 4

4-2

As shown in Table 4.A, you can control operation of memory
communication modules by using:

LIST functions (see page 4-3).
message (MSG) instructions (see page 4-16).

Typically, you use LIST functions during the development of your
application. This approach lets you select and deselect options manually.

In addition to providing additional selections, you can use message
instructions to automate memory communication module setup once you
are sure of the application. By inserting message instructions into the
ladder program, the memory communication module can be configured
automatically when powering up in the run mode or whenever the system
changes from program mode to run mode.

Table 4.A

LIST Functions and MSG Instructions

By Using:

You can:

LIST Function

MSG Instruction

transfer the contents of the data table from the

primary to the backup processor continuously

Yes

Yes

transfer the contents of selected files from the

primary to the backup processor continuously

Yes

Yes

transfer the contents of the data table from the

primary to the backup processor one time

No

Yes

transfer the contents of selected files from the

primary to the backup processor one time

No

Yes

stop further continuous transfers once the transfer

in progress completes

Yes

Yes

download memory from the primary to the backup

processor

Yes

Yes

control onĆline editing capability for a

programmable terminal

Yes

Yes

compare the ladder program in the backup

processor with the one in the primary processor

continuously

Yes

Yes

transfer control to the backup processor

No

Yes

inhibit the backup processor from taking control of

outputs when the primary processor faults

No

Yes

transfer backup processor data to the primary

processor

Yes

Yes

Controlling the Operation

of Memory Communication

Modules