Installing a Backup System

Chapter 2

2-7

You must configure all I/O chassis for backup mode operation. Each I/O
chassis has eight switches. Two of the switches, switches 2 and 8, are
especially important because they affect the operation of a backup system.
See Figure 2.4 for the function and location of the I/O chassis switches.

Figure 2.4

Location and Function of I/O Chassis Backplane Switches

1
2
3
4
5
6
7
8

Outputs of this I/O chassis remain in their last state when

a fault is detected by this I/O adapter.
Outputs of this I/O chassis are turned off when a fault is

detected by this I/O adapter.

ON

Switch

1. CAUTION: If you set this switch to the ON position, when a fault is detected, outputs connected to this

chassis remain in their last state to allow machine motion to continue. We recommend that you set

switch 1 to the OFF position to de - energize outputs wired to this chassis when a fault is detected.

2. The 1771 - AS adapter does not support 1 - slot or 1/2 - slot addressing. When you use this

adapter, set switches 5 and 6 to the OFF position.

3. The 1771 - ASB series A adapter does not support 1/2 - slot addressing.

NOTES:

Pressed in

at top Closed (ON)

Pressed in at

bottom Open (OFF)

5

OFF

ON

OFF

ON

6

OFF
OFF

ON
ON

2 - slot
1 - slot
1/2 - slot
Not allowed

Switches

1

1

OFF

Last State

The I/O chassis can be restarted from

the processor.
The processor is locked out from

restarting the I/O chassis after a fault.

ON

Switch

2

OFF

Processor Restart Lockout

Always On

Always On

Addressing

2

2, 3

16191

OFF ON

Configuring the I/O Chassis