Diagnosing Faults

Chapter 6

6-4

Table 6.B

Status Indicators for Backup Processor

Indicator

Status

Description

PROCESSOR

GREEN

Backup processor is active (normal operation in backup

mode)

RED

Major fault occurred

OFF

Power is off in the backup processor

OUTPUTS

GREEN

Not used

RED

Major fault*

OFF

Backup mode

PROGRAM

GREEN

Backup processor is in program load mode

RED

Major fault

1

OFF

Backup processor is not in program load mode

ACCESS

GREEN

A peripheral device is connected to a peripheral

communication channel and is onĆline (channel active).

RED

A peripheral device is editing the program or major fault

1

OFF

No peripheral communication channels are active.

1. When automatic switchover is selected, a major fault will turn all four status indicators red.

Diagnosing Faults with Module Status Indicators

All PLC-3 modules have two self-test indicators. Table 6.C describes how
to interpret these indicators.

Table 6.C

Module SelfĆTest Indicators

Indicator & Status

PASS

FAIL

Description

ON

OFF

Normal operation

OFF

ON

Module fault

ON

ON

PowerĆup or system reset

OFF

OFF

Processor shut off

Most PLC-3 modules have one or more indicators to help you pinpoint the
location of a fault. (See Figure 6.2 through Figure 6.4) Table 6.D through
Table 6.F describe how to interpret the indicators on each module.