Rockwell Automation 1775-MX_S4A,D17756.3.1 User Manual PLC-3 BACKUP CONC(OR.DU1 User Manual

Page 68

Advertising
background image

Using the 1775ĆMX

Memory Communication Module

Chapter 4

4-21

Table 4.I

Data Table Section Specifiers

Data Table Selection

Specifier

Output Image

O

Input Image

I

Timer

T

Counter

C

Integer

N

Floating Point

F

Decimal (BCD)

D

Binary

B

ASCII

A

High Order Integer

H

Pointers

P

Status

S

Important: Timers and counters cannot be separated into control, preset,
and accumulated value for the purpose of file transfers. In addition,
pointers cannot be separated into section, file, and word. Therefore, no file
number is necessary (although you can specify file 0).

For example, to add the timer section to the fifth position in the list, the
counter section to the sixth position, and the pointer section to the seventh
position in the list, type:

5/T

or

5/T0 [ENTER]

6/C

or

6/C0 [ENTER]

7/P

or

7/P0 [ENTER]

Figure 4.3 shows a rung for executing a continuous file transfer. It uses
integer file 2 and the timer section of the data table.

Advertising