Installing a Backup System

Chapter 2

2-23

Terminators

The first and last physical device of each I/O channel requires a terminator.
Use discrete terminators (cat. no. 1770-XT) for 1775-S4A, -SR scanner
modules. The 1775-S5, -SR5 scanner modules have internal terminators
that can be enabled/disabled with a switch. See Figure 2.17 and Figure 2.7.

Figure 2.17

Selecting Terminators on 1775ĆS5, ĆSR5 Scanner Modules

1

2

3

4

Switch Positions:

UP

= Switch is away from board

DOWN = Switch is toward board

When DOWN, a terminator is connected on the correĆ

sponding communication channel.

Connect a terminator when the scanner is physically

the first or last device on a Data Highway, Data HighĆ

way Plus, I/O, peerĆtoĆpeer, or backup communicaĆ

tions link; otherwise, set the switch to the UP position.

ON

OFF

ON

OFF

OFF

ON

10979ĆI

Important: When using internal terminators, removing the terminal
swing arm from a module causes the communication channels to be
unterminated.

For more information about terminators and I/O channel wiring, refer to
the PLC-3 Programmable Controller Installation and Operation Manual
(publication 1775-6.7.1).