Rockwell Automation 1775-MX_S4A,D17756.3.1 User Manual PLC-3 BACKUP CONC(OR.DU1 User Manual

Page 51

Advertising
background image

Using the 1775ĆMX

Memory Communication Module

Chapter 4

4-4

Figure 4.1

LIST Menu for Primary and Backup Processor

SYSTEM MODE
1

TEST MONITOR

2

* RUN MONITOR

3

PROGRAM LOAD

4

* REMOTE ENABLE

5

SYSTEM STATUS

6

MODULE STATUS

ENTER NEXT >

MODULES
1 01 1775-ME8 A/A
2 01 1775-L3 A/E
3 01 1775-S5 A/G
4 01 1775-MX A/C
ENTER NEXT >

MCM OPERATION
CHASSIS 00 SLOT 06
SYSTEM ID. 03
LIST CONTROL
1

INACTIVE

2

* FILE TRANSFER

3

DATA TABLE XFER

4

MEMORY DOWNLOAD

5

LOCK SYSTEM

6

* UNLOCK SYSTEM

7

ENABLE PROG COMP

8

* DISABLE PROG COMP

9

FILE SELECTION

10

PROG COMP LIMITS

11

BACKUP TO PRIMARY DATA TRANS-

FER
ENTER NEXT >

FILE SELECTIONS
1

O0

2

I0

3

N23

4

D2

5

T0

6

C0

ENTER NEXT >

PROG COMP LIMITS
0=COMP DISABLED
MAIN

00004

SUBROUTINE

00003

FAULT

00000

THIS FEATURE CAN ONLY BE ENABLED/DISABLED WHEN SYS-
TEM IS IN PROGRAM MODE. THIS FEATURE MUST BE CONFI-
GURED IDENTICALLY IN BOTH THE PRIMARY AND BACKUP MX
MODULES.

ENTER E TO ENABLE THIS FEATURE OR D TO DISABLE IT.

10980ĆI

The MCM OPERATION menu shows you three things:

the source of control functions
selections made in LIST
present operational status of the memory communication module

Chassis and slot information appear directly beneath the title of the menu.
A system identification number, which is derived from the chassis and slot
numbers of scanner number one, is also shown.