Diagnosing Faults

Chapter 6

6-6

Figure 6.4

Indicator Locations for 1775ĆMX Memory Communication Module

PASS and FAIL indicators

Status indicators

1775 - MX

Scanner

18752

Table 6.D

I/O Channel Indicators for All Scanner Modules

Indicator

Status

Description

CHx

ON

Communication between scanner module and the I/O

chassis on the corresponding I/O channel is properly

established.

Configured for I/O

Scanning

FLASHING

There is a fault on one or more of the I/O chassis on the

corresponding I/O channel.

OFF

No I/O chassis are configured on the corresponding I/O

channel or the channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

peerĆtoĆpeer

communication

FLASHING

The input file is too small at the processor receiving data.

The slave or master does not exist. Communication retry.

OFF

The channel is inactive.

CHx

ON

The channel is functioning properly.

Configured for

backup

communication

FLASHING

The input file is too small at the processor receiving data.

The partner is not responding.

OFF

The channel is inactive.