Diagnosing Faults

Chapter 6

6-13

Figure 6.7

Major Fault Bits

Stack fault

Deactive

Backup cable fault

Bad address

Bad instruction

Configuration fault
Memory parity error
Hardware fault
Major I/O fault
Watchdog timeout
Backplane fault
Bus extender fault
I/O configuration fault

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

11049-I

Automating the Diagnostics

If the PLC–3 system uses a 1775–GA peripheral communication module
or a 1775–S4B scanner module, you can program a procedure to display
the major fault and the possible rung at which the fault occurred.

For example, if you used the following procedure you would display
results as shown in Table 6.J.

@FAULT

1 A = $S9:0
2 B = A .BAND. 3
3 C = $S9:2
4 IF (C/00) PR ’SYSTEM CONFIGURATION FAULT’
5 IF (C/01) PR ’MEMORY PARITY ERROR’
6 IF (C/02) PR ’HARDWARE FAULT’
7 IF (C/03) PR ’MAJOR I/O FAULT’
8 IF (C/04) PR ’WATCHDOG TIMEOUT’
9 IF (C/05) PR ’BACKPLANE FAULT’
10 IF (C/06) PR ’BUS EXTENDER FAULT’
11 IF (C/07) PR ’I/O CONFIGURATION FAULT’
12 IF (C/010) PR ’DEACTIVE’
13 IF (C/011) PR ’BACKUP CABLE FAULT’
14 IF (C/014) PR ’BAD ADDRESS’
15 IF (C/015) PR ’BAD INSTRUCTION’
16 IF (C/017) PR ’STACK FAULT’
17 IF (B .EQ. 1) PR ’DETECTED AT RUNG RM’$S9:1
18 IF (B .EQ. 2) PR ’DETECTED AT RUNG RS’$S9:1
19 IF (B .EQ. 3) PR ’DETECTED AT RUNG RF’$S9:1
20 IF (C .EQ. 0) PR ’NO FAULT DETECTED’