Publication 1790-UM001A-EN-P - March 2002

Chapter

2

Installation and Wiring

This chapter tells you how to:

determine the power requirements for the modules

avoid electrostatic damage

install the module

wire the module’s terminal block

wire input devices

wire output devices

Power Requirements

The modules receive power through the DeviceNet network and from
an auxilary 24V dc field supply. The maximum power drawn by the
modules is shown in Table 2.1.

Module Installation

CompactBlock LDX is suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution

degree 2

(1)

) and to circuits not exceeding Over Voltage Category II

(2)

(IEC 60664-1).

(3)

Table 2.1
CompactBlock LDX Module Power Requirements

Voltage Range:

Power:

DeviceNet Power:

11-28.8 V dc

1.2W @ 28.8V dc

Auxilary 24V dc Field Power:

21.6-26.4V dc

1.5W @ 26.4V dc

(1)

Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.

(2)

Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.

(3)

Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)