Analog output data format, Output fault and idle states – Rockwell Automation 1790D-NOV2/TNOV2 CompactBlock LDX Analog Modules User Manual

Page 51

Advertising
background image

Publication 1790-UM001A-EN-P - March 2002

Module Data, Status, and Channel Configuration for Analog Output Modules 4-7

Analog Output Data Format

Analog output data is presented as raw/proportional. The full 12-bit
resolution is used over the entire span of the output full scale range,
as shown in Table 4.1.

Output Fault and Idle States

Analog output fault (communication failure) and idle (processor in
program mode) state can be defined for each output. Both fault state
and idle state can have the behavior defined in Table 4.2 for each
output.

The user-specified value is entered in raw/proportional notation. For
example:

0 is the low clamp. This value equals 0mA or oV dc.

4095 is the high clamp. This value equals 20mA or 10V dc.

Values between 0 and 4095 denote proportional values. 2048
equals 10mA or 5V dc.

The values in the output data file are retained. Once a fault or idle
condition is cleared, the retained output values are sent to the analog
output channels.

Table 4.1

Module:

Output Full Scale
Range:

HEX Data Range:

Decimal Data
Range:

Output Resolution:

1790D-NOV2/-TNOV2

0-10V dc

0000-0FFF

0-4095

2.44mV

1790D-N0C2/-TNOC2

0-20mA

0000-0FFF

0-4095

4.88

µ

A

Table 4.2

Behavior:

1790D-N0C2/-TN0C2:

1790D-N0V2/-TN0V2:

Go to low clamp

0mA

0V dc

Go to high clamp

20mA

10V dc

Go to fault/idle value

User configurable

User configurable

Hold last state

Hold last value

Hold last value