Connecting I/O Wiring

Consider the following guidelines when wiring your system:

General Guidelines

All module commons (ANLG COM) are connected in the analog
module. The analog common (ANLG COM) is not connected to
earth ground inside the module.

Channels are not isolated from each other.

Do not use the analog module’s NC terminals as connection
points.

To ensure optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system
as close to your sensors or actuators as your application will
permit.

Use Belden™ 8761, or equivalent, shielded wire.

Keep shield connection to ground as short as possible.

Under normal conditions, the drain wire and shield junction
must be connected to earth ground via a panel or DIN rail
mounting screw at the analog I/O module end.

Guidelines for Input Modules

If multiple power supplies are used with analog inputs, the
power supply commons must be connected together.

The module does not provide loop power for analog inputs. Use
a power supply that matches the input transmitter specifications.

Guidelines for Output Modules

Current outputs (CH0 and CH1) of the 1790P-TNOC2 module
source current that returns to COM. Load resistance for a current
output channel must remain between 0 and 600

.