Publication 1790-UM001A-EN-P - March 2002

5-4 Module Diagnostics and Troubleshooting

Channel Diagnostics

When an input or output module channel is enabled, the module
performs a diagnostic check to see that the channel has been properly
configured. In addition, the module checks each channel on every
scan for configuration errors, under-range, open-circuit (input module
in 4 to 20 mA range only).

Out-of-Range Detection (Input Modules Only)

An out-of-range low test is performed on all channels configured for
4-20mA inputs. Whenever an out-of-range low condition occurs, the
status bit for that channel is set in input data word 4.

Open-Circuit Detection (Input Module Only)

The module performs an open-circuit test on all channels configured
for 4 to 20 mA inputs. Whenever an open-circuit condition occurs, the
status bit for that channel is set in input data word 4.

Possible causes of an open circuit include:

the sensing device may be broken

a wire may be loose or cut

the sensing device may not be installed on the configured
channel